Building Control Systems
Smart controls that make HVAC simpler, cheaper and more reliable.

What we offer
We integrate building management and controls so heating, cooling and ventilation work together. Result: lower energy bills, fewer call-outs and a clear picture of how your plant is performing.
Building control systems here means the controls layer — the building management system with its sensors, controllers and field devices — rather than the local authority's building control department. It is the part of an installation that decides when plant runs, how hard it runs, and in response to what. Boilers, chillers, air handling units and fan coils are mostly obedient; they do what the controls tell them. Which is why a building with well-specified plant and neglected controls usually performs worse than an ordinary building with a strategy somebody has thought through.
Wasted energy tends to come down to a small set of recurring faults. Plant runs to a schedule written for an occupancy pattern that changed years ago. Control valves pass because actuators have failed in a mid position. Points sit in hand on a manual override applied during a call-out and never reversed, and a sensor reading somewhere unrepresentative quietly drags a whole zone with it. None of these register as breakdowns, so nobody reports them — the building simply uses more energy than it needs to and nobody can say why.
Scheduling is usually the first thing worth fixing. That means occupancy profiles per zone rather than one building-wide time clock, optimum start so the building reaches temperature by opening time instead of at four in the morning, optimum stop so it coasts on residual heat, and overnight setback rather than a hard off that forces a brutal morning recovery. Frost protection and holiday calendars are set explicitly. Where hot water is stored, the strategy must respect the temperature regime required for legionella control under ACOP L8.
A control system is only ever as good as what it measures. A sensor sited above a radiator, in direct sun or beside a doorway produces a comfortable-looking trend and an uncomfortable room. Return-air sensing in a fan coil reports mixed air rather than the occupied space. CO₂ sensors let ventilation modulate with real occupancy instead of running flat out for an empty meeting room, but they drift and need periodic calibration to stay honest. Zoning should follow how the building is used and where solar gain lands through the day.
Interlocks are the safety-critical half of controls and are treated as such. Air handling plant must shut down or change mode on a fire alarm signal, and dampers need end switches that prove position rather than assume movement. Commercial kitchens require a gas safety interlock under BS 6173 so the supply cannot stay live when the fans are not proving airflow. Frost coils, flow switches, drive run and fault signals and pump duty-standby changeover all belong in a documented strategy rather than in one person's memory.
Where controls are tired, recommissioning what already exists is usually the better first move: schedules corrected, sensors calibrated, overrides cleared, alarm priorities set, and the strategy written down so the next engineer inherits something. Where a genuine upgrade is warranted it can normally be phased, replacing the head end and controllers while retaining field devices that still work, so a site in Newbury, Thatcham or the wider West Berkshire area is not shut down for a rip-and-replace. Remote connections are configured to your IT policy rather than to whatever is quickest.
- BMS configuration, head-end setup and strategy documentation
- Time schedules, setbacks and optimum start/stop
- Zoning, sensor placement and calibration
- Fire, gas and plant interlocks tested and recorded
- BACnet, Modbus, KNX and Niagara integration
- Remote alarms, trend logging and energy reporting
- Phased upgrades to tired or proprietary controls
Common questions
- Why are our heating and cooling running at the same time?
- Almost always a controls problem rather than a plant fault. The usual causes are heating and cooling setpoints in the same zone with too narrow a dead band between them, a control valve passing because its actuator has failed mid-travel, or a sensor reading somewhere unrepresentative so two systems form different opinions about the same room. Trend logs normally identify which of the three it is within a few days.
- Our BMS was installed years ago and nobody uses it — replace it or recommission it?
- Recommission first in most cases. A surprising proportion of poor performance comes from schedules never updated after an occupancy change, overrides left in hand, drifted sensors and an undocumented strategy. Correcting those tells you what the existing system is genuinely capable of. If controllers then turn out to be closed, unsupported or failing, that finding justifies a phased upgrade on evidence rather than on assumption.
- Can a BMS genuinely reduce our energy use?
- Properly set schedules, dead bands, setbacks and optimised start and stop are among the more effective HVAC energy measures in a commercial building, because they stop plant running when nobody is there. How much difference it makes depends entirely on how badly the current setup behaves — a site already well controlled has little left to gain. Metering before and after is the only way to state a real figure.
- Can you bring equipment from different manufacturers onto one front end?
- Usually. BACnet, Modbus, KNX and M-Bus cover most modern plant, and a Niagara-based front end will present a mixed estate through a single interface. Legacy proprietary controllers may need a gateway, and a few closed systems cannot be integrated at all and have to be replaced. We survey what is on site and produce a points list before committing to an approach.
- Is remote access to our building controls a security risk?
- It is if it is done badly. Controls exposed directly to the internet on an open port are a well-documented weakness. Access should run through a VPN or a managed gateway, with named accounts, no shared default passwords, and the controls network segregated from your business network. We configure remote access to your IT team's policy and are happy for them to specify the arrangement.
- How do you stop nuisance alarms swamping the facilities team?
- By prioritising alarms and filtering the noise. Transient conditions during start-up should not raise the same alarm as a plant failure, delays and hysteresis stop devices chattering, and escalation routes send critical items to a person while informational ones go to a report. The aim is a small number of alarms that always mean something, because an inbox of hundreds is functionally the same as no alarms at all.
Related services
Ventilation Systems
Better airflow and indoor air quality, designed around your building.
Commercial HVAC
HVAC for offices, hotels, schools, restaurants and care environments.
Service & Maintenance
Planned maintenance that keeps systems running and avoids surprises.
Talk to an engineer today
Free consultation, fast quotes and 24/7 emergency cover.
Areas We Cover
Building Control Systems across Newbury, Reading, Basingstoke, Oxford, London and the wider South of England — covering Berkshire, Hampshire, Oxfordshire, Wiltshire, Dorset and Somerset.
